Experimental validation of a numerical model for an internal melt ice-on-coil thermal storage tank
Conference
·
OSTI ID:345218
- Centro Federal de Educacao Tecnologica de Minas Gerais, Belo Horizonte, Minas Gerais (Brazil). Dept. of Mechanical Engineering
- Univ. of Colorado, Boulder, CO (United States). Dept. of Civil, Environmental and Architectural Engineering
An internal melt ice-on-coil thermal storage tank was instrumented and tested over various inlet conditions of secondary fluid temperature and flow rate in a full-scale heating, ventilating, and air-conditioning (HVAC) laboratory. Five charging/discharging cycle tests were performed. The measured data for one typical charging/discharging cycle were used to validate a numerical model developed for analyzing internal melt ice-on-coil ice storage tanks. The validation analysis was based on the secondary fluid temperature leaving the tank, the secondary fluid heat transfer rates, the inventory of ice, the temperature of the secondary fluid at four representative locations along the coil, the temperature of the water and the ice at three representative locations inside the tank, and secondary fluid pressure drop through the tank. In general, good agreement was found between the predicted and the measured data.
- OSTI ID:
- 345218
- Report Number(s):
- CONF-9702141--
- Country of Publication:
- United States
- Language:
- English
Similar Records
Parametric analysis of an internal-melt ice-on-coil tank
Deterministic model for an internal melt ice-on-coil thermal storage tank
Baltimore Aircoil Company (BAC) Ice Storage Test Report
Conference
·
Tue Dec 30 23:00:00 EST 1997
·
OSTI ID:349968
Deterministic model for an internal melt ice-on-coil thermal storage tank
Conference
·
Tue Dec 30 23:00:00 EST 1997
·
OSTI ID:345217
Baltimore Aircoil Company (BAC) Ice Storage Test Report
Technical Report
·
Thu Feb 28 23:00:00 EST 1991
·
OSTI ID:5950615