Effect of an inclined angle on the heat transfer and pressure drop characteristics of a wavy-finned-tube heat exchanger

Conference ·
OSTI ID:33300
; ;  [1]
  1. Industrial Technology Research Inst., Hsinchu (Taiwan, Province of China). Energy and Resources Labs.

Experiments were carried out to investigate the heat transfer and pressure-drop characteristics of an inclined wavy-finned-tube heat exchanger. Two types of inclined configurations were examined for various frontal velocities. The heat transfer performance of the test coil was analyzed using the {epsilon}-NTU method. For forward-inclined coil, the test results indicate that the air-side heat transfer coefficient (h{sub o}) and the Colburn factor (j) decrease as the inclination angle rises. On the other hand, for the same face velocity, there is no measurable effect on the heat transfer performance for side inclination. However, the air-side pressure drop increases with an increase in the inclination angle for both forward and side-inclined configurations.

OSTI ID:
33300
Report Number(s):
CONF-9406105--
Country of Publication:
United States
Language:
English

Similar Records

Numerical predictions of wavy fin coil performance
Conference · Thu Jul 01 00:00:00 EDT 1999 · OSTI ID:20002462

Computer program for performance and sizing analysis of compact counter-flow plate-fin heat exchangers. Research and development report
Technical Report · Tue Nov 30 23:00:00 EST 1982 · OSTI ID:5607704

Experimental study of the air side performance of louver and wave fin-and-tube coils
Journal Article · Sat Jul 15 00:00:00 EDT 2006 · Experimental Thermal and Fluid Science · OSTI ID:20770217