skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Field experiments on occupant comfort and office thermal environments in a hot-humid climate

Conference ·
OSTI ID:33268
 [1];  [2]
  1. Macquarie Univ., Sydney (Australia). Climatic Impacts Centre
  2. Environmental Analytics, Piedmont, CA (United States)

This paper presents the main findings of ASHRAE research project RP-702, a field investigation of indoor climates and occupant comfort in 12 air-conditioned office buildings in Townsville, located in Australia`s tropical north. The project replicates an earlier ASHRAE investigation in San Francisco (RP-462). A total of 836 subjects provided 1,234 sets of questionnaire responses, each accompanied by a full set of physical indoor climatic measurements from laboratory-grade instrumentation. Clothing insulation estimates for seated subjects included the incremental effect of chairs. Thermal environmental results are compared with ASHRAE Standard 55-1992 prescriptions. Thermal neutrality, preference, and acceptability results are compared with laboratory-based models and standards. Gender and seasonal effects were minor, and many of the differences from the earlier San Francisco data were explicable in terms of clothing patterns. Most of the thermal dissatisfaction expressed within the Standard 55 comfort zone was associated with requests for higher air velocity.

OSTI ID:
33268
Report Number(s):
CONF-9406105-; TRN: IM9518%%89
Resource Relation:
Conference: 1994 American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) annual meeting, Orlando, FL (United States), 25-29 Jun 1994; Other Information: PBD: 1994; Related Information: Is Part Of ASHRAE transactions 1994: Technical and symposium papers. Volume 100, Part 2; PB: 1372 p.
Country of Publication:
United States
Language:
English