Low-frequency noise assessment metrics -- What do we know?
- Vipac Engineers and Scientists Ltd., Melbourne (Australia)
The issue of sound quality in offices and other occupied spaces has been of continuing interest since the 1950s. Existing assessment methods do not adequately account for the low-frequency background sound (< 250 Hz) produced by operating heating, ventilating, and air-conditioning (HVAC) systems, in particular, low-frequency rumble. This paper discusses the results of ASHRAE-sponsored research in which more than 75 HVAC noise samples were collected, normalized, and categorized in terms of sound quality. The results support previous findings that a neutral curve has a slope of approximately {minus}5 decibels (dB) per octave. There is also support for the contention that the balanced noise criterion B (NCB) curves are overly conservative in the region from 63 to 500 Hz and overly permissive below 63 Hz when compared with the room criteria (RC) curves. A modified set of room sound quality (RSQ) curves -- the room sound quality (RSQ) curves -- is proposed.