Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Calculation note: project W-320 primary ventilation air flowrequirements for mitigation of steady state flammable gasconcentrations in the headspaces of tanks 241-C-106 and 241-AY-102

Technical Report ·
DOI:https://doi.org/10.2172/328506· OSTI ID:328506

This calculation note analyzes headspace concentrations of hydrogen dependent upon assumed ventilation flow rates provided for tanks 241-C-106 and 241-AY-102. The analyses are based on measured or estimated steady state hydrogen release rates. Tank 241-C-106 is analyzed prior to sluicing; tank 241-AY-102 is analyzed both prior to and after completion of sluicing. Specific analyses, using both best estimated and bounding hydrogen generation rates, include the minimum primary ventilation flow rates required in the tanks to ensure that the steady state hydrogen concentration in the respective tank headspace does not exceed 25% and 100% of the LFL. The headspace hydrogen concentration as a function of time as well as the time required to reach 25% and 100% of LFL upon complete loss of active ventilation, starting from the steady state hydrogen concentration based on a 200 CFM minimum flow rate in tank 241-C-106 and a 100 CFM minimum flow rate in tank241-AY-102. The headspace hydrogen concentration as a function of thee following partial loss of active ventilation (i.e., step changes to l60, l20, 80, and 40 CFM ventilation flow rates) in tank 241-C-106, staffing from a 200 CFM flow rate and the corresponding steady state hydrogen concentration based on the 200 CFM flow rate. The headspace hydrogen concentration as a function of the following partial loss of active ventilation i.e., step changes to 80, 60, 40, and 20 CFM ventilation flow rates) in tank 241-AY-102, starting from a 100 CFM flow rate and the corresponding steady state hydrogen concentration based on the 100 CFM flow rate.

Research Organization:
Fluor Daniel Hanford, Inc., Richland, WA (United States)
Sponsoring Organization:
USDOE Office of Environmental Restoration and Waste Management, Washington, DC (United States)
DOE Contract Number:
AC06-96RL13200
OSTI ID:
328506
Report Number(s):
HNF-SD-WM-CN--114; ON: DE99050010; BR: EW3120074
Country of Publication:
United States
Language:
English

Similar Records

W-320 Project thermal modeling
Technical Report · Mon Mar 17 23:00:00 EST 1997 · OSTI ID:326424

System design description for portable 1,000 CFM exhauster Skids POR-007/Skid E and POR-008/Skid F
Technical Report · Sat Jul 25 00:00:00 EDT 1998 · OSTI ID:10148579

Interim safety equipment list for 241-C-106 waste retrieval, project W-320