ELM 1016706669-AA B581 GDE01 Generator Summary pg 4-5 only
- Lawrence Livermore National Laboratory (LLNL), Livermore, CA (United States)
The table below shows the general load breakdown for 581GDE01. Although the total connected load exceeds the generator’s 150kW nameplate capacity, the normal configured load during standby power mode is less, which was measured at 81kW, or 54%, during preventive maintenance activities on 12/12/24. The generator’s available spare capacity must account for dynamically changing loads that can increase the total power demand at any time. If the two online VFD’s are operated at full speed the actual standby mode load is estimated to increase by 38kW, which would bring the total configured load during standby power mode to 119kW, or 79%, still within 581GDE01’s acceptable capacity. Per the LLNL Site 200 Generator Consolidation Final Study 2022, “Standby Emergency Generator nameplate ratings are based upon operation with varying load averaging 70% of the nameplate for 200 hours per year. Continuous loading between 70% and 100% will reduce a generator’s expected lifetime before a major overhaul. This is never a problem with Laboratory machines because of conservative application of generators and the reliability of the normal power system combines to keeps the load and hours down”. To achieve optimal performance and prolong generator life, the recommended generator loading is between 40% and 70%, optimally at 70%, which 581GDE01 appropriately falls within.
- Research Organization:
- Lawrence Livermore National Laboratory (LLNL), Livermore, CA (United States)
- Sponsoring Organization:
- USDOE National Nuclear Security Administration (NNSA)
- DOE Contract Number:
- AC52-07NA27344
- OSTI ID:
- 3008386
- Report Number(s):
- LLNL--TR-2014201
- Country of Publication:
- United States
- Language:
- English
Similar Records
Costs of electric power outages to manufacturers
U. S. utilities missing out on synch mode of operation
Enhanced Component Performance Study: Motor Driven Pumps 1998–2022
Technical Report
·
Mon Nov 30 23:00:00 EST 1981
·
OSTI ID:5459516
U. S. utilities missing out on synch mode of operation
Journal Article
·
Wed Dec 31 23:00:00 EST 1975
· Gas Turbine World; (United States)
·
OSTI ID:7223532
Enhanced Component Performance Study: Motor Driven Pumps 1998–2022
Technical Report
·
Sat Jul 01 00:00:00 EDT 2023
·
OSTI ID:2301600