Recovery time of superconducting non-inductive reactor type fault current limiter

Journal Article · · IEEE Transactions on Magnetics
DOI:https://doi.org/10.1109/20.511357· OSTI ID:287655
; ;  [1]; ;  [2]
  1. Saga Univ., Honjo, Saga (Japan)
  2. Kyushu Electric Power Co., Kono-Higashi, Saga (Japan)

A superconducting fault current limiting device for electric power systems has been investigated to find out its feasibility. Non-inductive reactor type fault current limiter has been constructed using metal superconductor. Two bifilar wound solenoids were connected in antiparallel or antiseries. On each connection, the fault current limiting test was performed by short-circuiting a resistive load suddenly. The recovery (normal-to-superconductive state transition) time after the current limiting mode has been studied using small scale model of fault current limiter for the low voltage distribution line. The results reveal that the current limiter could be operated under repetitive fault current accident which was removed within a few cycle of the limiting mode. The recovery time is a function of the dissipated energy under current limiting mode. Test results are presented.

OSTI ID:
287655
Report Number(s):
CONF-950691--
Journal Information:
IEEE Transactions on Magnetics, Journal Name: IEEE Transactions on Magnetics Journal Issue: 4Pt1 Vol. 32; ISSN IEMGAQ; ISSN 0018-9464
Country of Publication:
United States
Language:
English

Similar Records

Fabrication and Tests of a Resistive-Type Superconducting Fault Current Limiter Module Based on Coated Conductors
Journal Article · Sat Jun 15 00:00:00 EDT 2019 · Journal of Superconductivity and Novel Magnetism · OSTI ID:22921238

Passive fault current limiting device
Patent · Thu Dec 31 23:00:00 EST 1998 · OSTI ID:872248

Passive fault current limiting device
Patent · Tue Apr 06 00:00:00 EDT 1999 · OSTI ID:335474