CEBAF has undergone a major conversion of its accelerator control system from TACL to EPICS, affecting device control for the RF system, magnets, the machine protection system, the vacuum and valves, and the diagnostic systems including beam position monitors, harps, and the camera and solenoid devices (beam viewers, faraday cups, optical transition radiation viewers, synchrotron radiation monitor, etc.). Altogether these devices require approximately 125,000 EPICS database records. The majority of these devices are controlled through CAMAC; some use embedded microprocessors (RF and magnets), and newer interfaces are in VME. The standard EPICS toolkit was extended to include a driver for CAMAC which supports dual processors on one serial highway, custom database records for magnets and BPMs, and custom data acquisition tasks for the BPMs. 2 refs., 1 tab.