Using transformer differential relay I{sub op} characteristics to measure near-trip conditions
Conference
·
OSTI ID:277504
- Basler Electric Co., Highland, IL (United States)
When a transformer differential relay operates with no obvious transformer fault, system operators have a serious decision to make: is there a transformer fault, or did the relay trip incorrectly? Testing the transformer requires significant time, with associated costs. However, re-energizing a faulted transformer can lead to catastrophic failure. This scenario of a questionable transformer trip occurs too often, especially during the commissioning of new transformers and/or differential relays. Usually a differential relay false trip is caused by either incorrect settings or incorrect current transformer (CT) secondary lead connections. These conditions can cause false trips for external faults, or simply transformer loading. Some indication is needed that the relay is not operating as desired, before an incorrect trip happens. A potential problem can be discovered by monitoring the operating condition of the differential relay. An indicator can serve as a warning if the settings or connections are not correct.
- OSTI ID:
- 277504
- Report Number(s):
- CONF-960509--; ISBN 0-7803-3263-6
- Country of Publication:
- United States
- Language:
- English
Similar Records
Analysis of misoperation of the differential current relay applied in a Y-Y-Y-{Delta} transformer
13. 8-kV (ground) fault-bus-relaying study
Application of Advanced Wide Area Early Warning Systems with Adaptive Protection
Conference
·
Fri Sep 01 00:00:00 EDT 1995
·
OSTI ID:94253
13. 8-kV (ground) fault-bus-relaying study
Conference
·
Fri Dec 31 23:00:00 EST 1982
·
OSTI ID:6348632
Application of Advanced Wide Area Early Warning Systems with Adaptive Protection
Technical Report
·
Fri May 01 00:00:00 EDT 2015
·
OSTI ID:1184190