Title: A computer program to perform dynamic thermal analysis for bare overhead conductors during short-time overload conditions

Conference ·
OSTI ID:269844
;  [1]
  1. ELCON Associates, Inc., Portland, OR (United States)

Under emergency conditions, a bare overhead conductor can carry an increased amount of current that is well in excess of its normal rating. When there is this increase in current flow on a bare overhead conductor, the temperature does not rise instantaneously. but increases along a curve determined by the current, the conductor properties and the ambient conditions. The conductor temperature at the end of a short-time overload period must be restricted to its maximum design value. This paper presents a simplified approach in analyzing the dynamic performance for bare overhead conductors during short-time overload condition. A computer program was developed to calculate the short-time ratings for bare overhead conductors. The following parameters: current induced heating. solar load, convective/conductive cooling, radiative cooling, altitude, wind velocity and ampacity of the bare conductor were considered. Several sample graphical output lots are included with the paper.

OSTI ID:
269844
Report Number(s):
CONF-951050-; TRN: 96:002072-0018
Resource Relation:
Conference: Conference of the Institute of Electrical and Electronics Engineers, Inc., Portland, OR (United States), 10-12 Oct 1995; Other Information: PBD: 1995; Related Information: Is Part Of IEEE technical applications conference and workshops - Northcon/95; PB: 430 p.
Country of Publication:
United States
Language: