Low-NOx burner and SNCR retrofit experience at New England Power Salem Harbor Station
Technical Report
·
OSTI ID:269425
- Fossil Energy Research Corp., Laguna Hills, CA (United States)
- New England Power Co., Westborough, MA (United States)
New England Power has recently installed Riley-Stoker low-NO{sub x} burners (LNB) and Nalco Fuel Tech urea-based selective non-catalytic NO{sub x} reduction (SNCR) systems on Units 1 and 3 at its Salem Harbor generating station. In addition, Unit 3 was also retrofit with a two-level overfire air (OFA) system. These two coal-fired units are front wall-fired with unequal burner spacing and have uncontrolled full-load NO{sub x} emissions of nominally 750 ppm (1.1 lb/MMBtu). Unit 1 is rated at 86 MW and has 12 burners, while Unit 3 is rated at 155 MW and has 16 burners. NO{sub x} reduction performance of the LNB, OFA and SNCR systems has been characterized both independently and in combination during the test programs while firing low-sulfur coals. Unit 1 tests showed that the LNBs provided NO{sub x} reductions of approximately 50 percent at loads above 60 MW using narrow angle coal spreaders. Corresponding ash carbon at these NO{sub x} levels varied between 16 and 35 percent. The SNCR system provided an additional 40 percent NO{sub x} reduction from the LNB baseline at a molar N/NO ratio of 1.2. The corresponding NH{sub 3} slip levels were less than 10 ppm. On Unit 3, LNB tests showed that NO{sub x} reductions of nominally 10 percent were achieved with the burners alone, using wide angle coal spreaders. The use of OFA, at design levels, provided additional NO{sub x} reductions ranging from 42 percent at full load to 4 percent a minimum load relative to the LNB baseline. Ash carbon levels doubled to levels above 30 percent when the OFA system was operated at design conditions at loads above 110 MW. The SNCR system provided NO{sub x} reductions of 33 percent relative to the LNB/OFA baseline of 0.55 lb/MMBtu, at a molar N/NO ratio of 1.3. Ammonia slip for these conditions was less than 5 ppm.
- Research Organization:
- Electric Power Research Inst., Palo Alto, CA (United States)
- OSTI ID:
- 269425
- Report Number(s):
- EPRI-TR--105978-V1; CONF-9505150--Vol.1
- Country of Publication:
- United States
- Language:
- English
Similar Records
Cardinal Unit 1 large scale selective non-catalytic reduction demonstration project
NOx Control for Utility Boiler OTR Compliance
Commercial application of urea SNCR for NO{sub x} RACT compliance on a 112 MWe pulverized coal boiler
Conference
·
Thu Jul 01 00:00:00 EDT 1999
·
OSTI ID:20082325
NOx Control for Utility Boiler OTR Compliance
Technical Report
·
Sat Jul 30 00:00:00 EDT 2005
·
OSTI ID:963897
Commercial application of urea SNCR for NO{sub x} RACT compliance on a 112 MWe pulverized coal boiler
Technical Report
·
Sun Dec 31 23:00:00 EST 1995
·
OSTI ID:269415