Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Modeling of out-of-step conditions in power systems

Journal Article · · IEEE Transactions on Power Systems
DOI:https://doi.org/10.1109/59.496163· OSTI ID:264254
;  [1];
  1. Kiev Polytechnic Inst. (Ukraine). Dept. of Electrical Power Engineering
The out-of-step protective relays are employed for detecting out-of-step conditions in power systems. The relay parameter setting requires simulations of expected out-of-step conditions. Here, the out-of-step conditions are modeled as a periodic motion, and are represented analytically by the Fourier series. The Fourier coefficients are computed using numerical iterations. A two-level iteration process is developed to obtain periodic bus-voltage dynamics. The computed bus voltages are used next to derive and to plot apparent impedance and line power loci needed for the out-of-step relay parameter setting. The proposed techniques are illustrated using an example of the National Power Company of Ukraine.
OSTI ID:
264254
Report Number(s):
CONF-950727--
Journal Information:
IEEE Transactions on Power Systems, Journal Name: IEEE Transactions on Power Systems Journal Issue: 2 Vol. 11; ISSN 0885-8950; ISSN ITPSEG
Country of Publication:
United States
Language:
English

Similar Records

A New Out-of-Step Relay with Rate of Change of Apparent Resistance Augmentation.
Journal Article · Mon Feb 28 23:00:00 EST 1983 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5977916

Adaptive out-of-step relaying using phasor measurement techniques
Journal Article · Fri Oct 01 00:00:00 EDT 1993 · IEEE Computer Applications and Power; (United States) · OSTI ID:5617445

An adaptive out-of-step relay
Journal Article · Tue Dec 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:477186