Effect of Transverse Compression on the Dielectric Breakdown of Power Cable with Ethylene Propylene Rubber Insulation
- ORNL
Understanding of the failure mechanisms of submarine dynamic power cables (SDPC) is critical for innovative design to meet the 2035 cost reduction target of U.S. DOE Floating Offshore Wind Shot. This is important because the current design suffers a significant failure rate in the field. This project explored a multiphysics approach and conducted systematic electro-thermo-mechanical (ETM) experimental study on the power cores extracted from a 15 kV power cable. The power cable had three cores of copper conductor and ethylene propylene rubber (EPR) insulation. An ETM testing system with transverse compression capability was developed. Mechanical loading induced dielectric breakdown. Increasing temperature from room temperature (RT, 22 degrees Celsius) to 90 degrees Celsius resulted in the 67% decrease in the failure mechanical load as defined by the dielectric breakdown. With the same temperature rise, the creep mechanical load was reduced by 70% at a given dielectric breakdown time. The post-test measurement revealed an impressive recovery of electrical resistance, although the dielectric breakdown occurred in the ETM test that would not be captured without the use of ETM testing.
- Research Organization:
- Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE); USDOE
- DOE Contract Number:
- AC05-00OR22725
- OSTI ID:
- 2586910
- Country of Publication:
- United States
- Language:
- English
Similar Records
Electro-Thermo-Mechanical (ETM) Study on Submarine Dynamic Power Cables (SDPC) for Offshore Wind Transmission
Advanced Diagnostics and Life Estimation of Extruded Dielectric Cable: Nonproprietary Results Related to Cross-Linked Polyethylene and Ethylene Propylene Rubber Insulated Shielded Cables
An assessment of field aged 15 and 35kV ethylene propylene rubber insulated cables
Technical Report
·
Fri Jan 31 23:00:00 EST 2025
·
OSTI ID:2573352
Advanced Diagnostics and Life Estimation of Extruded Dielectric Cable: Nonproprietary Results Related to Cross-Linked Polyethylene and Ethylene Propylene Rubber Insulated Shielded Cables
Technical Report
·
Thu Mar 30 23:00:00 EST 2006
·
OSTI ID:878894
An assessment of field aged 15 and 35kV ethylene propylene rubber insulated cables
Journal Article
·
Sat Dec 31 23:00:00 EST 1994
· IEEE Transactions on Power Delivery
·
OSTI ID:39966