Transient Stability Analysis of Direct Droop-Controlled Grid-Forming Inverter with Current Clipping as Current Limiting Control
- BATTELLE (PACIFIC NW LAB)
This paper investigates the transient stability of the direct droop-controlled grid-forming (GFM) inverter which employs the current clipping-based approach for overcurrent limitation. An equivalent circuit model of the direct-droop GFM inverter with current clipping is developed for this purpose. It is shown that during overcurrent conditions, the GFM inverter with current clipping acts as a voltage source with a virtual resistance behind the inverter filters. To compute the parameters of this virtual resistance an analytical expression is given in the paper. Then utilizing the developed circuit, a criteria to exit current limiting during post-fault conditions is given. The developed analytical approaches are then validated through electromagnetic transient (EMT) simulation results in PSCAD software and finally concluding remarks are drawn.