A Preliminary Investigation on the Performance of a Dual-Source Heat Pump using both the Air and the Ground
Conference
·
OSTI ID:2491448
- ORNL
Air source heat pumps (ASHPs) and ground source heat pumps (GSHPs) are the two most common types of electric-driven heat pumps in the marketplace to replace fossil fuel-based heating systems. However, the performance and efficiency of ASHPs depend on the ambient air conditions. Therefore, ASHPs usually are equipped with electric resistance heaters to provide supplemental heating when the ambient temperature is low, and the heating demand is high. The electric resistance heaters could result in high power draws when they are turned on. On the other hand, due to the relatively steady temperature of the ground, GSHPs are more energy efficient than ASHPs when providing space heating and cooling to the buildings. However, the adoption of GSHP is hindered by its high initial cost, mostly due to the cost of drilling boreholes for installing ground heat exchangers (GHE). To solve the above issues, our study investigates the performance of dual-source heat pumps (DSHPs) with respect to that of ASHPs and GSHPs. The DSHP will use ambient air when its temperature is favorable for the efficient operation of the heat pump. When the ambient temperature is too hot or too cold, the ground source will be utilized to retain the high-efficiency operation of the heat pump. Because the cumulative thermal load of the GHE is shared with the ambient air, the size of the GHE could be smaller than those of the conventional GSHPs. The study will model the DSHP and simulate its performance in providing heating and cooling for a typical single-family house in regions with hot, mild, or cold climates. In addition, the required GHE size of the DSHP system will be determined through annual simulations and compared with that of conventional GSHPs.
- Research Organization:
- Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE; USDOE Office of Energy Efficiency and Renewable Energy (EERE)
- DOE Contract Number:
- AC05-00OR22725
- OSTI ID:
- 2491448
- Country of Publication:
- United States
- Language:
- English
Similar Records
An economic and technical feasibility analysis of a dual-source heat pump using both the air and the ground
Experimental performance analysis of a dual source heat pump integrated with thermal energy storage
Comparative performance assessment of air-source and ground-source heat pumps using CO₂ and R-410A with water well integration: A simulation study
Journal Article
·
Mon Nov 10 19:00:00 EST 2025
· Energy and Buildings
·
OSTI ID:3004288
Experimental performance analysis of a dual source heat pump integrated with thermal energy storage
Conference
·
Wed Nov 30 23:00:00 EST 2022
·
OSTI ID:1909081
Comparative performance assessment of air-source and ground-source heat pumps using CO₂ and R-410A with water well integration: A simulation study
Journal Article
·
Tue Oct 21 20:00:00 EDT 2025
· Journal of Building Engineering
·
OSTI ID:3002363