End-Use Savings Shapes Measure Documentation: Thermostat Control for Load Shifting in Large Offices
- National Renewable Energy Laboratory (NREL), Golden, CO (United States)
This documentation focuses on a single end-use savings shape measure - thermostat control for load shifting. The thermostat control for load shifting measure applies heating and cooling temperature setpoint adjustment for pre-conditioning before the peak window. The measure takes daily peak load schedule inputs generated by the method "Dispatch Schedule Generation" described in the "Supplemental Documentation: Dispatch Schedule Generation for Demand Flexibility Measures" to determine the start time of the peak window, and then adjusts the thermostat cooling or heating setpoints by a specified offset value from original schedules to precool or preheat the space , for a specified length of time before the start of peak window, and thus shifts load in the peak window to the pre-conditioning period. The measure is flexible and allows users to adjust the heating and cooling offset values and length of pre-conditioning period, but for this study, the load shifting strategy is applied as pre-cooling only (adjusting only cooling setpoints). The default adjustment for cooling setpoints is set to -1 degrees Celsius , and the default duration of pre-cooling is 1 hour. This measure is applicable to large offices equipped with electric HVAC system, which account for approximately 8.72% of the ComStock floor area. The thermostat control for load shifting measure demonstrates -1% daily peak demand reduction and 0% total site energy savings (0 trillion British thermal units [TBtu]) for the U.S. commercial building stock modeled in ComStock.
- Research Organization:
- National Renewable Energy Laboratory (NREL), Golden, CO (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
- DOE Contract Number:
- AC36-08GO28308
- OSTI ID:
- 2349285
- Report Number(s):
- NREL/TP--5500-89341; MainId:90120; UUID:6d1c03da-6bce-4aed-8034-1ff2b616a205; MainAdminId:72561
- Country of Publication:
- United States
- Language:
- English
Similar Records
End-Use Savings Shapes Measure Documentation: Thermostat Control for Load Shedding in Large Offices
ComStock Measure Documentation: Thermostat and Lighting Control for Load Shedding
ComStock Measure Documentation: Thermostat and Lighting Control for Load Shedding + Photovoltaics With 40% Rooftop Coverage
Technical Report
·
Mon May 06 00:00:00 EDT 2024
·