Measured effects of retrofits -- a refrigerant oil additive and a condenser spray device -- on the cooling performance of a heat pump

Conference ·
OSTI ID:226035
A 15-year old, 3-ton single package air-to-air heat pump was tested in laboratory environmental chambers simulating indoor and outdoor conditions. After documenting initial performance, the unit was retrofitted with a prototype condenser water-spray device and retested. Results at standard ARI cooling rating conditions (95 F outdoor dry bulb and 80/67 F indoor dry bulb/wet bulb temperatures) showed the capacity increased by about 7%, and the electric power demand dropped by about 8%, resulting in a steady-state EER increase of 17%. Suction and discharge pressures were reduced by 7 and 37 psi, respectively. A refrigerant oil additive formulated to enhance refrigerant-side heat transfer was added at a dose of one ounce per ton of rated capacity, and the unit was tested for several days at the same 95 F outdoor conditions and showed essentially no increase in capacity, and a slight 3% increase in steady-state EER. Adding more additive lowered the EER slightly. Suction and discharge pressures were essentially unchanged. The short-term testing showed that the condenser-spray device was effective in increasing the cooling capacity and lowering the electrical demand on an old and relatively inefficient heat pump, but the refrigerant additive had little effect on the cooling performance of the unit. Sprayer issues to be resolved include the effect of a sprayer on a new, high-efficiency air conditioner/heat pump, reliable long-term operation, and economics.
Research Organization:
Oak Ridge National Lab., TN (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC05-96OR22464
OSTI ID:
226035
Report Number(s):
CONF-9603161--1; ON: DE96008645
Country of Publication:
United States
Language:
English

Similar Records

Test of condensate subcooling coils for air conditioners
Conference · Sun Dec 31 23:00:00 EST 1989 · OSTI ID:6343770

Operating performance of a water spray on an air-type condensing unit
Conference · Wed Dec 31 23:00:00 EST 1980 · ASHRAE Trans.; (United States) · OSTI ID:6388810

Experimental study of a liquid overfeeding window air conditioner
Book · Thu Oct 31 23:00:00 EST 1996 · OSTI ID:392434