ASME AG-1 Section FC Qualified HEPA Filters; a Particle Loading Comparison - 13435
Conference
·
OSTI ID:22225057
- Camfil Farr, 1 North Corporate Drive, Riverdale, NJ 07457 (United States)
- New Mexico State University, Department of Engineering Technology and Surveying Engineering, P.O. Box 30001 MSC 3566, Las Cruces, NM 88003-8001 (United States)
High Efficiency Particulate Air (HEPA) Filters used to protect personnel, the public and the environment from airborne radioactive materials are designed, manufactured and qualified in accordance with ASME AG-1 Code section FC (HEPA Filters) [1]. The qualification process requires that filters manufactured in accordance with this ASME AG-1 code section must meet several performance requirements. These requirements include performance specifications for resistance to airflow, aerosol penetration, resistance to rough handling, resistance to pressure (includes high humidity and water droplet exposure), resistance to heated air, spot flame resistance and a visual/dimensional inspection. None of these requirements evaluate the particle loading capacity of a HEPA filter design. Concerns, over the particle loading capacity, of the different designs included within the ASME AG-1 section FC code[1], have been voiced in the recent past. Additionally, the ability of a filter to maintain its integrity, if subjected to severe operating conditions such as elevated relative humidity, fog conditions or elevated temperature, after loading in use over long service intervals is also a major concern. Although currently qualified HEPA filter media are likely to have similar loading characteristics when evaluated independently, filter pleat geometry can have a significant impact on the in-situ particle loading capacity of filter packs. Aerosol particle characteristics, such as size and composition, may also have a significant impact on filter loading capacity. Test results comparing filter loading capacities for three different aerosol particles and three different filter pack configurations are reviewed. The information presented represents an empirical performance comparison among the filter designs tested. The results may serve as a basis for further discussion toward the possible development of a particle loading test to be included in the qualification requirements of ASME AG-1 Code sections FC and FK[1]. (authors)
- Research Organization:
- WM Symposia, 1628 E. Southern Avenue, Suite 9-332, Tempe, AZ 85282 (United States)
- OSTI ID:
- 22225057
- Report Number(s):
- INIS-US--13-WM-13435
- Country of Publication:
- United States
- Language:
- English
Similar Records
Results from Evaluation of Representative ASME AG-1 Section FK Radial Flow Dimple Pleated HEPA Filters Under Elevated Conditions - 12002
Evaluating the Performance Envelope of Axial Flow HEPA Filter Designs - 17466
Performance Evaluation of Axial Flow AG-1 FC and Prototype FM (High Strength) HEPA Filters - 13123
Conference
·
Sun Jul 01 00:00:00 EDT 2012
·
OSTI ID:22293355
Evaluating the Performance Envelope of Axial Flow HEPA Filter Designs - 17466
Conference
·
Sat Jul 01 00:00:00 EDT 2017
·
OSTI ID:22802453
Performance Evaluation of Axial Flow AG-1 FC and Prototype FM (High Strength) HEPA Filters - 13123
Conference
·
Mon Jul 01 00:00:00 EDT 2013
·
OSTI ID:22224905