Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Design and experimental investigation of an ejector in an air-conditioning and refrigeration system

Conference ·
OSTI ID:211812
 [1];  [2]
  1. Silesian Technical Univ., Gliwice (Poland). Mechanical Engineering Dept.
  2. Univ. of Sibrata (Libyan Arab Jamahiriya). Mechanical Engineering Dept.

This paper discusses the conservation of energy in a refrigerant ejector refrigerating machine using heat driven from the concentrator collectors. The working refrigerant was R-113. The design of an ejector operating in an air-conditioning and refrigerating system with a low thermal source (70 C to 100 C) is presented. The influence of three major parameters--boiler, condenser, and evaporator temperature--on ejector efficiency is discussed. Experimental results show that the condenser temperature is the major influence at a low evaporator temperature. The maximum ejector efficiency was 31%.

OSTI ID:
211812
Report Number(s):
CONF-950624--
Country of Publication:
United States
Language:
English