Protocol for field testing of tall buildings to determine envelope air leakage rate
Conference
·
OSTI ID:20085600
The objective of this project was to develop a relatively simple, accurate method for testing the overall envelope leakage rate of tall buildings. Two fan pressurization test techniques, the floor-by-floor blower door method and the air-handler method, were developed and tested on two buildings. Criteria for conducting accurate tests were developed, including limitations on outdoor air temperature and wind speed. The floor-by-floor blower door method permits isolation and measurement of the leakage flow rate of a single floor, but it is difficult and time-consuming to apply. The air-handler method uses building air distribution fans for pressurization. It is most easily applied on a system-by-system level rather than floor-by-floor. fan airflow techniques including orifice plate, pitot traverse, and tracer gas dilution were considered. The tracer gas method was found to be relatively easy to apply and highly accurate. Fan airflow rate measurement uncertainty by tracer gas was estimated to be 5.4% to 8.8% for the cases considered, assuming a 5% uncertainty in interzonal leakage.
- Research Organization:
- Pennsylvania State Univ., University Park, PA (US)
- OSTI ID:
- 20085600
- Country of Publication:
- United States
- Language:
- English
Similar Records
Predicting Envelope Leakage in Attached Dwellings (Fact Sheet)
Stack effect in tall buildings
Blower-door techniques for measuring interzonal leakage
Technical Report
·
Fri Nov 01 00:00:00 EDT 2013
·
OSTI ID:1114061
Stack effect in tall buildings
Conference
·
Fri Dec 30 23:00:00 EST 1994
·
OSTI ID:33265
Blower-door techniques for measuring interzonal leakage
Conference
·
Mon Dec 31 23:00:00 EST 2012
·
OSTI ID:1167386