The analysis of an ungrounded Wye-Delta transformer bank serving an induction motor and single-phase lighting loads

Journal Article · · IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers)
DOI:https://doi.org/10.1109/28.821794· OSTI ID:20020636
This paper documents the detailed analysis of the three-phase ungrounded wye-delta transformer bank serving a combination three-phase induction motor and single-phase lighting load. A 3 x 3 transfer function matrix is developed that makes it possible to determine the load line-to-line voltages with a knowledge of the primary voltages of the transformer bank. Included in the transfer function matrix are the transformer impedances, unsymmetrical secondary impedance matrix, and the impedances of the motor and single-phase lighting load.
Research Organization:
New Mexico State Univ., Las Cruces, NM (US)
Sponsoring Organization:
US Department of Energy
OSTI ID:
20020636
Journal Information:
IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers), Journal Name: IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers) Journal Issue: 1 Vol. 36; ISSN 0093-9994; ISSN ITIACR
Country of Publication:
United States
Language:
English