skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Numerical investigation of convective heat transfer and pressure drop in wavy ducts

Journal Article · · Numerical Heat Transfer. Part A, Applications

The search for a plate geometry with the best ratio of heat transfer to pressure drop is the most important aspect of plate heat exchanger design. Here, flow field and heat transfer in corrugated ducts have been investigated from the numerical solutions of the Navier-Stokes equations in the laminar to transitional range of Reynolds numbers (600--2,000). First, the geometric parameters for the best ratio of heat transfer to pressure drop have been determined for two-dimensional channels. Then for these parameters, flow structure and heat transfer have been investigated for three-dimensional (3-D) channels consisting of corrugated plates. The angles 45{degree} and 90{degree} between the corrugations and the main stream direction have been considered. A performance evaluation criterion identifies the 3-D corrugated plate at 45{degree} with the best ratio between heat transfer and pressure drop.

Research Organization:
Hengst Filterwerke, Muenster (DE)
OSTI ID:
20014338
Journal Information:
Numerical Heat Transfer. Part A, Applications, Vol. 37, Issue 1; Other Information: PBD: Jan 2000; ISSN 1040-7782
Country of Publication:
United States
Language:
English