Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Some observations of foaming characteristics in the nucleate boiling performance of refrigerant-oil mixtures

Conference ·
OSTI ID:20002329

This paper discusses the effect of lubricant oil on nucleate boiling performance for a smooth tube. The lubricant oil used in the investigation includes 3GS and 5GS, and the working refrigerant is R-22. Experiments were conducted at saturation temperatures of {minus}5 C, 4.4 C, and 20 C. For refrigerant-oil mixtures, the heat transfer coefficients, h, decrease with increase of oil concentrations at T{sub s} = 20 C. Conversely, for T{sub s} = {minus}5 C, the heat transfer coefficients for refrigerant-oil mixtures may be larger than those of pure refrigerants at low oil concentration. Possible explanations for this phenomenon include (1) the effect of physical properties, especially that of surface tension, and (2) foaming characteristics.

Research Organization:
Industrial Technology Research Inst., Hsinchu (TW)
OSTI ID:
20002329
Report Number(s):
CONF-990102--; ISSN 0001-2505
Country of Publication:
United States
Language:
English

Similar Records

Nucleate pool boiling of refrigerant-oil mixtures
Conference · Thu Dec 31 23:00:00 EST 1981 · Am. Soc. Mech. Eng., (Pap.); (United States) · OSTI ID:5303267

Prediciton of nucleate pool boiling heat transfer coefficients of refrigerant-oil mixtures
Journal Article · Tue Jan 31 23:00:00 EST 1984 · J. Heat Transfer; (United States) · OSTI ID:6752037

Nucleate boiling performance of refrigerants and refrigerant-oil mixtures
Journal Article · Fri Oct 31 23:00:00 EST 1980 · J. Heat Transfer; (United States) · OSTI ID:6721053