Common Cause Failure Evaluation of High Safety Significant Safety-related Digital Instrumentation and Control Systems using IRADIC Technology

Conference ·
OSTI ID:1983618
Digital instrumentation and control (DI&C) systems in nuclear power plants (NPPs) have many advantages over analog systems but also pose different engineering and technical challenges, such as potential threats due to common cause failures (CCFs). This paper proposes an integrated risk assessment technology for DI&C systems (IRADIC) developed by Idaho National Laboratory for dealing with potential software CCFs in DI&C systems of NPPs. The methodology development of the IRADIC technology on the quantitative evaluation of software CCFs in high safety-significant safety-related DI&C systems in NPPs is illustrated in this paper. In IRADIC, qualitative hazard analysis and quantitative reliability and consequence analysis are successively implemented to obtain quantitative risk information, compare with respective risk evaluation acceptance criteria, and provide suggestions for risk reduction and design optimization. A comprehensive case study was also performed and documented in this paper. Results show that the IRADIC technology can effectively identify potential digital-based CCFs, estimate their failure probabilities, and evaluate their impacts to system and plant safety.
Research Organization:
Idaho National Laboratory (INL), Idaho Falls, ID (United States)
Sponsoring Organization:
USDOE Office of Nuclear Energy (NE)
DOE Contract Number:
AC07-05ID14517
OSTI ID:
1983618
Report Number(s):
INL/CON-22-65562-Rev001
Country of Publication:
United States
Language:
English