Performance analysis of single-phase immersion cooling system of data center using FC-40 dielectric fluid
Journal Article
·
· International Communications in Heat and Mass Transfer
- National Yang Ming Chiao Tung University (Taiwan); Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- National Yang Ming Chiao Tung University (Taiwan)
Immersion cooling technologies have become an emerging cooling method for data center cooling. The studies available in open literature dealt with immersion cooling performance of data servers using mineral oil, EC-100, and Opticool 872552, but the studies focusing on the performance of FC-40 dielectric fluid is not available. Therefore, this study aimed to develop a single-phase liquid immersion cooling system using FC-40 dielectric fluid for a 1U (44.45 mm height) data server. The present study experimentally investigated the influence of different design and operating parameters, including the inlet/outlet port configuration (T and Z configurations), the bypass effect, the flowrate (1–3 LPM), the heating load (200–600 W), the inlet fluid temperature (15–35 °C), the presence of suction fan with various arrangements, and different heat sink bases (solid base, vapor chamber and heat pipe base). The results showed that the T-configuration could provide a 12.6% and 0.5–2.8 °C reduction in thermal resistance and case temperature compared to the Z-configuration, respectively. Additionally, the heat sink with heat pipe and vapor chamber base offered a minimum case temperature of 56.7 °C and 55.2 °C against the 60 °C experienced in the heat sink with flat plate base, respectively.
- Research Organization:
- Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE
- Grant/Contract Number:
- AC05-00OR22725
- OSTI ID:
- 1975331
- Journal Information:
- International Communications in Heat and Mass Transfer, Journal Name: International Communications in Heat and Mass Transfer Journal Issue: B Vol. 145; ISSN 0735-1933
- Publisher:
- ElsevierCopyright Statement
- Country of Publication:
- United States
- Language:
- English
Similar Records
Forced convection behavior of a dielectric fluid (FC-77) in a 2:1 rectangular duct
Fluid heating attachment for automobile engine cooling systems
PINCH POINT ANALYSIS OF GAS COOLERS IN TRANSCRITICAL R1336mzz(Z) HIGH-TEMPERATURE HEAT PUMPS
Journal Article
·
Sun Sep 01 00:00:00 EDT 1996
· International Communications in Heat and Mass Transfer
·
OSTI ID:267954
Fluid heating attachment for automobile engine cooling systems
Patent
·
Mon Mar 10 23:00:00 EST 1986
·
OSTI ID:5899953
PINCH POINT ANALYSIS OF GAS COOLERS IN TRANSCRITICAL R1336mzz(Z) HIGH-TEMPERATURE HEAT PUMPS
Conference
·
Mon Apr 01 00:00:00 EDT 2024
·
OSTI ID:2438954