Assessment of the Phase-to-Ground Fault Apparent Admittance Method with Phase/Ground Boundaries to Detect Types of Electrical Faults for Protective Relays Using Signature Library and Simulated Events

Journal Article · · International Transactions on Electrical Energy Systems
DOI:https://doi.org/10.1155/2022/1951836· OSTI ID:1889502
 [1];  [2];
  1. Power Systems Resilience Group, Electrification and Energy Infrastructures Division, Oak Ridge National Laboratory, Oak Ridge, Tennessee 37830, USA
  2. Solar Energy Technologies Office, US Department of Energy, Washington D.C. 20585, USA

Protective relays in electric power grids recognize the types of electrical faults in a few seconds. The most common detection method to detect the types of electrical faults is based on measuring the angle between the zero and negative sequence currents. However, it is not completely accurate because the phase-to-phase-ground and phase-to-ground electrical faults could have the same detection conditions. Therefore, engineers need to plot the events after an electrical fault to observe the nature of the incidents in detail. In this study, the phase-to-ground fault apparent (PGFA) admittance method with phase/ground boundaries identified the types of electrical faults located in distribution power lines and feeders. This method was based on measuring the PGFA admittance magnitudes for the faulted and nonfaulted phases, resulting in greater than zero and near zero, respectively. The PGFA admittance algorithm was built with MATLAB/Simulink software and tested with signature library and grid simulation events. The PGFA method with phase/ground boundaries was evaluated with the confusion matrix. The measured and predicted values matched in more than 90% of the tests, and the PGFA admittance method with phase/ground boundaries presented an accuracy of 94.3% and a precision of 100%.

Research Organization:
Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
USDOE
Grant/Contract Number:
AC05-00OR22725
OSTI ID:
1889502
Alternate ID(s):
OSTI ID: 1892432
Journal Information:
International Transactions on Electrical Energy Systems, Journal Name: International Transactions on Electrical Energy Systems Vol. 2022; ISSN 2050-7038
Publisher:
Hindawi Publishing CorporationCopyright Statement
Country of Publication:
United States
Language:
English

References (14)

Protection schemes used in North American microgrids journal May 2020
Comparison of high‐speed adaptive and nonadaptive backup overcurrent protection on fuse feeders with sensors
  • Piesciorovsky, Emilio Carlos; Ferrari Maglia, Maximiliano F.
  • International Transactions on Electrical Energy Systems, Vol. 29, Issue 4 https://doi.org/10.1002/etep.2812
journal December 2018
Comparison of Programmable Logic and Setting Group Methods for adaptive overcurrent protection in microgrids journal October 2017
Modeling the impact of GIC neutral blocking devices on distance protection relay operations for transmission lines journal March 2020
Effects of the fault inception angle in fault-induced transients journal May 2012
The Fault Causes of Overhead Lines in Distribution Network journal January 2016
A Comparative Review of Fault Location/Identification Methods in Distribution Networks conference June 2018
Distance elements: Linking theory with testing conference March 2009
Determining the faulted phase conference March 2010
Understanding the dynamic mho distance characteristic conference April 2016
Current-Based Trip Coil Analysis of Circuit Breakers for Fault Diagnosis conference October 2018
Under voltage accelerated protection of single source distribution systems conference January 2003
A Real-Time Data-Driven Algorithm for Health Diagnosis and Prognosis of a Circuit Breaker Trip Assembly journal June 2015
Detecting Single-Phase-to-Ground Fault Event and Identifying Faulty Feeder in Neutral Ineffectively Grounded Distribution System journal October 2018