skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Results of a field test of heating system efficiency and thermal distribution system efficiency in a manufactured home

Technical Report ·
DOI:https://doi.org/10.2172/188595· OSTI ID:188595
; ;  [1]; ;  [2]
  1. Brookhaven National Lab., Upton, NY (United States)
  2. Synertech Systems Corp., Syracuse, NY (United States)

A two-day test using electric coheating was performed on a manufactured home in Watertown, New York. The main objective of the test was to evaluate planned procedures for measuring thermal distribution system efficiency. (Thermal distribution systems are the ductwork or piping used to transport heat or cooling effect from the equipment that produces it to the building spaces in which it is used.) These procedures are under consideration for a standard method of test now being prepared by a special committee of the American Society of Heating, Refrigerating, and Air-Conditioning Engineers. The ability of a coheating test to give a credible and repeatable value for the overall heating system efficiency was supported by the test data. Distribution efficiency is derived from system efficiency by correcting for energy losses from the equipment. Alternative means for achieving this were tested and assessed. The best value for system efficiency in the Watertown house was 0.53, while the best value for distribution efficiency was 0.72.

Research Organization:
Brookhaven National Lab. (BNL), Upton, NY (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC02-76CH00016
OSTI ID:
188595
Report Number(s):
BNL-62362; ON: DE96003676; TRN: AHC29604%%72
Resource Relation:
Other Information: PBD: May 1995
Country of Publication:
United States
Language:
English