Multi-objective optimization of low-GWP mixture composition and heat exchanger circuitry configuration for improved system performance and reduced refrigerant flammability

Journal Article · · International Journal of Refrigeration

The recently introduced hydrofluoroolefin (HFO) refrigerants, including R1234yf and R1234ze(E), have significantly lower global warming potentials (GWPs) than traditional hydrofluorocarbon (HFC) refrigerants like R410A. However, prior tests show that direct drop-in of pure R1234yf or R1234ze(E) into equipment designed for R410A results in a decrease in heat exchanger capacity and the system coefficient of performance. The primary reason is the lower in-tube heat transfer performance of R1234yf and R1234ze(E) compared with that of R410A. To address this issue, previous studies have mixed the mildly flammable HFC R32 with HFOs to improve system performance, with HFC R125 also added to suppress flammability. Previous studies selected compositions based on simple cycle analyses and did not consider modifications of the heat exchanger circuitry configuration to adapt to the new refrigerants. This study presents a novel multi-objective optimization approach to design a refrigerant composition that maximizes energy efficiency within flammability and GWP limits. The approach in this work simultaneously optimizes mixture composition and heat exchanger circuitry configuration. A case study on a rooftop unit indicates that, compared with mixture-only optimization, simultaneous optimization of mixture and heat exchanger circuitry yields a 5.9% improvement in cycle efficiency and a 48.6% reduction in refrigerant flammability with a GWP of 268. Circuitry optimization using refrigerants with different temperature glides shows that the larger the temperature glide is, the larger EER improvement is obtained. The results show that zeotropic blends with a large temperature glide are more sensitive to the refrigerant circuitry than pure refrigerants and may suffer significant performance degradation with subpar heat exchanger circuitry design. The proposed optimization approach is generally applicable to mixtures with any number of components. Using this approach to design a HVAC system can yield higher system efficiency within flammability and GWP constraints.

Research Organization:
Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE)
Grant/Contract Number:
AC05-00OR22725
OSTI ID:
1785210
Alternate ID(s):
OSTI ID: 1777522
Journal Information:
International Journal of Refrigeration, Journal Name: International Journal of Refrigeration Journal Issue: 1 Vol. 126; ISSN 0140-7007
Publisher:
ElsevierCopyright Statement
Country of Publication:
United States
Language:
English

References (11)

Heat transfer in automobile radiators of the tubular type journal January 1985
Condensation in horizontal tubes, part 2: new heat transfer model based on flow regimes journal August 2003
Heat transfer and friction correlation for compact louvered fin-and-tube heat exchangers journal June 1999
Rooftop air-conditioning unit performance improvement using refrigerant circuitry optimization journal May 2015
Investigation of flow boiling in horizontal tubes: Part II—Development of a new heat transfer model for stratified-wavy, dryout and mist flow regimes journal July 2005
Low-GWP refrigerants for medium and high-pressure applications journal December 2017
Model-based optimizations of packaged rooftop air conditioners using low global warming potential refrigerants journal March 2018
Low GWP halocarbon refrigerants: A review of thermophysical properties journal June 2018
Tube-fin heat exchanger circuitry optimization using integer permutation based Genetic Algorithm journal July 2019
An empirical model for refrigerant flammability based on molecular structure and thermodynamics journal August 2019
Limited options for low-global-warming-potential refrigerants journal February 2017