Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Power Restoration Design - Building 1010 & 1010A

Technical Report ·
DOI:https://doi.org/10.2172/1761978· OSTI ID:1761978
 [1]
  1. Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)
Power distribution upgrades that include: A new PMH-5, 12KV/208, Delta/WYE transformer. 600A Main Switchboard (MSB) with 600A LSI Main CB and push button capability. New feeders from transformer to MSB. New panels with NEMA 1 enclosures, door-in-door, with 4" gutter space on each side, New NEMA 4X CT Cabinet and meter socket. New 300A & 150A LSI circuit breakers, Trenching for grounding and an allowance of $12,000 for grounding system provided by SNL electrical Operations Engineer.
Research Organization:
Sandia National Laboratories (SNL-NM), Albuquerque, NM (United States)
Sponsoring Organization:
USDOE National Nuclear Security Administration (NNSA)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
1761978
Report Number(s):
SAND--2016-12265R-Rev.01; 674126