Performance Simulation and Analysis of Occupancy-Based Control for Office Buildings with Variable-Air-Volume Systems

Journal Article · · Energies
DOI:https://doi.org/10.3390/en13153756· OSTI ID:1668800
 [1];  [2];  [2];  [1]
  1. Univ. of North Carolina, Charlotte, NC (United States)
  2. Pacific Northwest National Lab. (PNNL), Richland, WA (United States)
Variable-air-volume (VAV) systems are used in many office buildings. The minimum airflow rate setting of VAV terminal boxes has a significant impact on both energy consumption and indoor air quality. Conventional controls usually have the terminal’s minimum airflow rate at a constant (e.g., 30% or more of the terminal design airflow rate), irrespective of the occupancy status, which may cause problems, such as excessive simultaneous heating and cooling, under ventilation, and thermal comfort issues. This paper examines the potential of energy savings from occupancy-based controls (OBCs). The sensed occupancy information, either occupant presence or people count, is used to determine the airflow rate of terminal boxes, the thermostat setpoints, and the lighting control. Using EnergyPlus, a whole-building energy modeling software, the energy savings of OBC strategies are evaluated for representative existing medium office buildings in the U.S. The simulation results show that the conventional OBC, based on occupant presence sensing, can save 8% of whole-building energy use in Miami (hot climate) for systems without air-side economizer and about 13% in both Baltimore (mixed climate) and Chicago (cold climate). Comparatively, the advanced OBC, based on people counting, can save 8% in Miami to 23% in Baltimore for systems with economizers. The outdoor-air fraction of the supply air from air-handling units significantly affects the potential energy savings from the advanced OBC strategy. In addition to energy savings, the advanced OBC satisfies the zone ventilation during all occupied hours over the whole year.
Research Organization:
Pacific Northwest National Laboratory (PNNL), Richland, WA (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
Grant/Contract Number:
AC05-76RL01830
OSTI ID:
1668800
Report Number(s):
PNNL-SA--153601
Journal Information:
Energies, Journal Name: Energies Journal Issue: 15 Vol. 13; ISSN 1996-1073
Publisher:
MDPI AGCopyright Statement
Country of Publication:
United States
Language:
English

References (17)

Importance of occupancy information for building climate control journal January 2013
Occupancy-based zone-climate control for energy-efficient buildings: Complexity vs. performance journal June 2013
Minimum airflow reset of single duct VAV terminal boxes journal September 2009
Modeling occupancy in single person offices journal February 2005
A generalised stochastic model for the simulation of occupant presence journal January 2008
A novel and dynamic demand-controlled ventilation strategy for CO2 control and energy saving in buildings journal September 2011
A study on the control method of single duct VAV terminal unit through the determination of proper minimum air flow journal February 2014
Occupancy measurement in commercial office buildings for demand-driven control applications—A survey and detection system evaluation journal April 2015
Characterizing variations in variable air volume system controls journal January 2017
An Analysis of the Energy and Cost Savings Potential of Occupancy Sensors for Commercial Lighting Systems journal July 2001
Ventilation Control Strategy Using the Supply CO2 Concentration Setpoint journal April 2005
Demand controlled ventilation for multiple zone HVAC systems: CO 2 -based dynamic reset (RP 1547) journal November 2014
Implementation and comparison of existing occupant behaviour models in EnergyPlus journal November 2015
Experimental evaluation of occupancy-based energy-efficient climate control of VAV terminal units journal March 2015
Sentinel: occupancy based HVAC actuation using existing WiFi infrastructure within commercial buildings conference January 2013
U.S. Department of Energy Commercial Reference Building Models of the National Building Stock report February 2011
Implementation and comparison of existing occupant behaviour models in EnergyPlus collection January 2015

Figures / Tables (12)