Low-Frequency Stability Analysis of Inverter-Based Islanded Multiple-Bus AC Microgrids Based on Terminal Characteristics
Journal Article
·
· IEEE Transactions on Smart Grid
- Danfoss LLC, Tallahassee, FL (United States)
- Univ. of Tennessee, Knoxville, TN (United States)
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
For system planning of three-phase inverter-based islanded ac microgrids, the low frequency instability issue caused by interactions of inverter droop controllers is a major concern. When internal control information of procured commercial inverters is unknown, impedance-based small-signal stability criteria facilitate prediction of resonances in medium and high frequency ranges, but they usually assume the grid fundamental frequency as constant and thus they are incapable of analyzing the low-frequency oscillation of the fundamental frequency in islanded microgrids. Aiming at solving this issue, this paper proposes two stability analysis methods based on terminal characteristics of inverters and passive connection network including the dynamics of the fundamental frequency for analysis of low-frequency stability in islanded multiple-bus microgrids. Based on the Component Connection Method (CCM) to systematically separate inverters from the passive connection network, a general approach is developed to model the microgrid as a multiple-input-multiple-output (MIMO) negative feedback system in the common system d-q reference frame. By applying the generalized Nyquist stability criterion (GNC) to the return-ratio and return-difference matrices of the MIMO system model, the low-frequency stability related to the fundamental frequency can be analyzed using the measured terminal characteristics of inverters. Finally, analysis and simulation of a 37-bus microgrid verify the effectiveness of the proposed stability analysis methods.
- Research Organization:
- Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE Office of Electricity Delivery and Energy Reliability (OE)
- Grant/Contract Number:
- AC05-00OR22725
- OSTI ID:
- 1648986
- Journal Information:
- IEEE Transactions on Smart Grid, Journal Name: IEEE Transactions on Smart Grid Journal Issue: 5 Vol. 11; ISSN 1949-3053
- Publisher:
- IEEECopyright Statement
- Country of Publication:
- United States
- Language:
- English
Similar Records
D–Q Impedance Based Stability Analysis and Parameter Design of Three-Phase Inverter-Based AC Power Systems
A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-based Resources
A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-Based Resources
Journal Article
·
Tue Mar 14 00:00:00 EDT 2017
· IEEE Translations on Industrial Electronics
·
OSTI ID:1394533
A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-based Resources
Conference
·
Sun Oct 09 00:00:00 EDT 2022
· 2022 IEEE Industry Applications Society Annual Meeting (IAS)
·
OSTI ID:2222584
A Stability Analysis Tool for Bulk Power Systems Using Black-Box Models of Inverter-Based Resources
Journal Article
·
Wed Aug 02 20:00:00 EDT 2023
· IEEE Transactions on Industry Applications
·
OSTI ID:2222571