Analysis of MTDC Inertia Emulation Impact on Connected AC Systems
Conference
·
· IEEE Energy Conversion Congress and Exposition (ECCE)
- The University of Tennessee, Knoxville
- University of Tennessee, Knoxville (UTK)
- ORNL
The frequency decoupling effect of the voltage source converter (VSC)-based high voltage dc (HVDC) transmission makes frequency support unavailable between two ac subsystems interconnected by the HVDC link. Recently, several algorithms have been proposed and demonstrated to improve the ac system stability by implementing inertia emulation (IE) functions in the HVDC VSC stations. However, the capability of the VSC-HVDC to achieve the IE control is not clear. According to the previous research, the IE control strategy has been studied without concerning the impact of the practical control process, which will introduce some time delay into the IE realization. In this paper, a detailed multi-terminal HVDC VSC control module, including the phase-locked loop (PLL) and low pass filter (LPF), is considered in order to analyze the multi-terminal HVDC network impact on the IE performance. The analysis indicates that the frequency performance of the ac network with IE integrated HVDC transmission can be nearly as good as that directly connected with the ac subsystem which involves a high penetration of conventional generation units, except for the short time delay introduced by the VSC control modules. The effectiveness of IE performance will be compromised if the response delay is significant. The simulation results have verified the analysis.
- Research Organization:
- Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE
- DOE Contract Number:
- AC05-00OR22725
- OSTI ID:
- 1546545
- Conference Information:
- Journal Name: IEEE Energy Conversion Congress and Exposition (ECCE) Journal Volume: 2018
- Country of Publication:
- United States
- Language:
- English
Similar Records
Mixed Monopole and Bipole MTdc Architecture
Models and Methods for Assessing the Value of HVDC and MVDC Technologies in Mondern Power Grids
Control of MMC-HVDC in low-inertia weak grids
Conference
·
Sun Oct 01 00:00:00 EDT 2023
·
OSTI ID:2281140
Models and Methods for Assessing the Value of HVDC and MVDC Technologies in Mondern Power Grids
Technical Report
·
Sun Sep 01 00:00:00 EDT 2019
·
OSTI ID:1566996
Control of MMC-HVDC in low-inertia weak grids
Conference
·
Thu Nov 30 23:00:00 EST 2017
·
OSTI ID:1423061