Innovations in polymer arrester moisture sealing testing

Conference ·
OSTI ID:152762
; ;  [1]
  1. Raychem Corp., Menlo Park, CA (United States)
The vast majority of porcelain distribution arrester failures are the result of moisture ingress. Standards lag technology and do not currently address the unique design aspects of polymer arresters. Traditional sealing test methods cannot be run on polymer arresters because of lack of internal air space. A novel design test is proposed which involves sensitive interfacial leakage current measurements as the diagnostic. Samples are thermally cycled in water to produce thermal excursions and aging, while encouraging water ingress, should the sealing system be compromised. The proposed test is a modification of a protocol established for polymer insulators, which has been correlated to field service.
OSTI ID:
152762
Report Number(s):
CONF-9404175--; ISBN 0-7803-1883-8
Country of Publication:
United States
Language:
English

Similar Records

Innovation in polymer arrester moisture sealing testing
Journal Article · Sat Dec 31 23:00:00 EST 1994 · IEEE Transactions on Power Delivery · OSTI ID:39980

Evaluation of polymer-housed distribution arresters for use on rural electric power systems
Journal Article · Mon Feb 28 23:00:00 EST 1994 · IEEE Transactions on Industry Applications · OSTI ID:7153937

Utilization of polymer enclosed intermediate class arresters to improve the performance of modern power systems
Journal Article · Wed Jul 01 00:00:00 EDT 1992 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:7050515