Desiccant degradation in desiccant cooling systems: A system study
Journal Article
·
· Journal of Solar Energy Engineering
- National Renewable Energy Lab., Golden, CO (United States)
The authors predict the impact of desiccant degradation on the performance of an open-cycle desiccant cooling system in ventilation mode using the degradation data on silica gel obtained from a previous study. The degradation data were based on thermal cycling desiccant samples and exposing them to ambient or contaminated air. Depending on the degree of desiccant degradation, the decrease in the thermal coefficient of performance (COP) and the cooling capacity of the system for low-temperature regeneration was 10 percent to 35 percent. The 35 percent loss occurred based on the worst-case desiccant degradation scenario. Under more realistic conditions the loss in system performance is expected to be lower.
- Sponsoring Organization:
- USDOE
- OSTI ID:
- 143939
- Journal Information:
- Journal of Solar Energy Engineering, Journal Name: Journal of Solar Energy Engineering Journal Issue: 4 Vol. 115; ISSN JSEEDO; ISSN 0199-6231
- Country of Publication:
- United States
- Language:
- English
Similar Records
Desiccant degradation in desiccant cooling systems: An experimental study
Impact of desiccant degradation on desiccant cooling system performance
Desiccant contamination in desiccant cooling systems
Journal Article
·
Sun Oct 31 23:00:00 EST 1993
· Journal of Solar Energy Engineering
·
OSTI ID:143935
Impact of desiccant degradation on desiccant cooling system performance
Conference
·
Sat Sep 01 00:00:00 EDT 1990
·
OSTI ID:6489190
Desiccant contamination in desiccant cooling systems
Conference
·
Wed Aug 01 00:00:00 EDT 1990
·
OSTI ID:6797115