Open Secondary Testing of Window-Type Current Transformers
- Brookhaven National Laboratory (BNL), Upton, NY (United States)
Two AMRAN Current Transformers (CTs) were tested to characterize the propensity of an opencircuited CT secondary to cause a fire in a location remote to the open circuit. Also evaluated was the magnitude of the secondary winding peak (crest) voltage when the CT’s secondary circuit transitioned to an open circuit condition, and its dependencies on the primary voltage, primary current and the CT’s turn ratio.