Case Study for the ARRA-funded GSHP Demonstration at Furman University

Technical Report ·
DOI:https://doi.org/10.2172/1408657· OSTI ID:1408657
 [1];  [1]
  1. Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)

With funding provided by the American Recovery and Reinvestment Act, 26 ground source heat pump (GSHP) projects were competitively selected in 2009 to demonstrate the benefits of GSHP systems and innovative technologies for cost reduction and/or performance improvement. One of the selected demonstration projects was proposed by Furman University for ten student housing buildings—the North Village located on the campus in Greeneville, South Carolina. All ten buildings are identical in floor plan and construction. Each building is conditioned by an identical GSHP system consisting of 25 water-to-air heat pump (WAHP) units, a closed-loop vertical ground heat exchanger (GHX) installed under an adjacent parking lot, and two redundant 7.5 hp variable-speed pumps to circulate water through the GHX and the WAHPs. The actual performance of the GSHP systems is analyzed with available measured data for 2014. The annual energy performance is compared with a baseline scenario in which the building is conditioned by air-source heat pumps (ASHPs) with the minimum allowed efficiencies specified in ASHRAE Standard 90.1-2013 (SEER 13 for cooling and 7.8 HSPF for heating) and supplemental electric heaters. The comparison is made in terms of energy savings, operating cost savings, cost-effectiveness, and environmental benefits. Finally, limitations in conducting this analysis are identified and recommendations for further improving the operational efficiency of the GSHP systems are made.

Research Organization:
Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC05-00OR22725
OSTI ID:
1408657
Report Number(s):
ORNL/TM-2015/472
Country of Publication:
United States
Language:
English

Similar Records

Case Study for the ARRA-funded GSHP Demonstration at University at Albany
Technical Report · Sat Jan 31 23:00:00 EST 2015 · OSTI ID:1185868

Case Study of The ARRA-Funded GSHP Demonstration at the Natural Sources Building, Montana Tech
Technical Report · Sun Nov 30 23:00:00 EST 2014 · OSTI ID:1185865

Case Study for ARRA-funded Ground-Source Heat Pump (GSHP) Demonstration at Oakland University
Technical Report · Tue Sep 01 00:00:00 EDT 2015 · OSTI ID:1215575