R290 (propane) and R600a (isobutane) as natural refrigerants for residential heat pump water heaters
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
Growing awareness of the potential environmental impacts of various refrigerants has led to the phasedown of hydrofluorocarbon (HFC) refrigerants and to initiatives replacing HFCs with hydrocarbons or other environmentally friendlier fluids. Here, this study evaluated the performance of R290 (propane) and R600a (isobutane) as substitutes for R134a (a HFC) for heat pump water heating (HPWH). A component-based model (calibrated against the experimental data) was used to predict the performance of the HPWH system. Key performance parameters such as unified energy factor, first hour rating, condenser discharge temperature, thermal stratification in the water tank, and total refrigerant charge were investigated. Analysis results suggest that both alternative refrigerants could provide comparable system performance to that of the baseline system containing R134a, with one caveat. Finally, as a drop-in alternative, R290 was found to be a better substitute for R134a, whereas R600a is expected to provide similar performance if the compressor size is increased to provide similar heating capacity. Significant reductions in system charge and lower condenser discharge temperatures were identified as additional benefits.
- Research Organization:
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
- Sponsoring Organization:
- USDOE
- DOE Contract Number:
- AC05-00OR22725
- OSTI ID:
- 1394289
- Journal Information:
- Applied Thermal Engineering, Vol. 127, Issue C; ISSN 1359-4311
- Publisher:
- Elsevier
- Country of Publication:
- United States
- Language:
- English
Similar Records
Energy Efficiency and Performance Evaluation of Self-Contained, Medium Temperature, Reach-In Refrigerated Display Cases
Flow condensation heat transfer performance of natural and emerging synthetic refrigerants