Determining the Impact of Steady-State PV Fault Current Injections on Distribution Protection

Technical Report ·
DOI:https://doi.org/10.2172/1367427· OSTI ID:1367427
This report investigates the fault current contribution from a single large PV system and the impact it has on existing distribution overcurrent protection devices. Assumptions are made about the modeling of the PV system under fault to perform exhaustive steady - state fault analyses throughout distribution feeder models. Each PV interconnection location is tested to determine how the size of the PV system affects the fault current measured by each protection device. This data is then searched for logical conditions that indicate whether a protection device has operated in a manner that will cause more customer outages due to the addition of the PV system. This is referred to as a protection issue , and there are four unique types of issues that have been identified in the study. The PV system size at which any issues occur are recorded to determine the feeder's PV hosting capacity limitations due to interference with protection settings. The analysis is carried out on six feeder models. The report concludes with a discussion of the prevalence and cause of each protection issue caused by PV system fault current.
Research Organization:
Sandia National Laboratories (SNL-NM), Albuquerque, NM (United States)
Sponsoring Organization:
USDOE National Nuclear Security Administration (NNSA)
DOE Contract Number:
AC04-94AL85000
OSTI ID:
1367427
Report Number(s):
SAND2017-4955; 653195
Country of Publication:
United States
Language:
English

Similar Records

Convolutional Neural Network-Based Protection-Zone Classification of Faults in Distribution Feeders with Photovoltaics.
Conference · Thu May 09 00:00:00 EDT 2024 · OSTI ID:2426426

Investigation of Ground-Fault Protection Devices for Photovoltaic Power Systems Applications
Conference · Tue Oct 03 00:00:00 EDT 2000 · OSTI ID:764900

Detection of arcing faults on distribution feeders. Final report
Technical Report · Tue Nov 30 23:00:00 EST 1982 · OSTI ID:6609328