Evaluation of Variable Refrigerant Flow Systems Performance on Oak Ridge National Laboratory s Flexible Research Platform: Part 2 Heating Season Analysis

Technical Report ·
DOI:https://doi.org/10.2172/1356895· OSTI ID:1356895
 [1];  [1];  [1]
  1. Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States)
The performance of two HVAC systems was evaluated using ORNL’s FRP, which is a two-story, 3,200 ft2 (297.3 m2) multi-zone unoccupied building that represents a typical low-rise, small office building common in the US existing building stock. The FRP is equipped with a conventional 12.5 ton (44 kW) RTU-VAV reheat system as the baseline system. For this study, a 12 ton (42 kW) VRF with a dedicated outdoor air system (DOAS) was installed to be compared with the baseline RTU system.