Title: Modeling of Protection in Dynamic Simulation Using Generic Relay Models and Settings

Conference ·

This paper shows how generic protection relay models available in planning tools can be augmented with settings that are based on NERC standards or best engineering practice. Selected generic relay models in Siemens PSS®E have been used in dynamic simulations in the proposed approach. Undervoltage, overvoltage, underfrequency, and overfrequency relays have been modeled for each generating unit. Distance-relay protection was modeled for transmission system protection. Two types of load-shedding schemes were modeled: underfrequency (frequency-responsive non-firm load shedding) and underfrequency and undervoltage firm load shedding. Several case studies are given to show the impact of protection devices on dynamic simulations. This is useful for simulating cascading outages.

Research Organization:
Pacific Northwest National Lab. (PNNL), Richland, WA (United States)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC05-76RL01830
OSTI ID:
1339046
Report Number(s):
PNNL-SA-114479; TE1103000
Resource Relation:
Conference: IEEE Power and Energy Society General Meeting (PESGM 2016), July 17-21, 2016, Boston, MA
Country of Publication:
United States
Language:
English

Similar Records

Dynamic Contingency Analysis Tool
Software · Thu Jan 14 00:00:00 EST 2016 · OSTI ID:1339046

Modeling Zone-3 Protection with Generic Relay Models for Dynamic Contingency Analysis
Conference · Mon Oct 02 00:00:00 EDT 2017 · OSTI ID:1339046

Generator ground fault protection using overcurrent, overvoltage, and undervoltage relays
Journal Article · Wed Dec 01 00:00:00 EST 1982 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:1339046