Title: Pioneering Heat Pump Project

Abstract

This project was initiated at a time when ground coupled heat pump systems in this region were limited in size and quantity. There were economic pressures with costs for natural gas and electric utilities that had many organizations considering ground coupled heat pumps; The research has added to the understanding of how ground temperatures fluctuate seasonally and how this affects the performance and operation of the heat pumps. This was done by using a series of temperature sensors buried within the middle of one of the vertical bore fields with sensors located at various depths below grade. Trending of the data showed that there is a lag in ground temperature with respect to air temperatures in the shoulder months, however as full cooling and heating season arrives, the heat rejection and heat extraction from the ground has a significant effect on the ground temps; Additionally it is better understood that while a large community geothermal bore field serving multiple buildings does provide a convenient central plant to use, it introduces complexity of not being able to easily model and predict how each building will contribute to the loads in real time. Additional controllers and programming were added to provide moremore » insight into this real time load profile and allow for intelligent shedding of load via a dry cooler during cool nights in lieu of rejecting to the ground loop. This serves as a means to ‘condition’ the ground loop and mitigate thermal creep of the field, as is typically observed; and It has been observed when compared to traditional heating and cooling equipment, there is still a cost premium to use ground source heat pumps that is driven mostly by the cost for vertical bore holes. Horizontal loop systems are less costly to install, but do not perform as well in this climate zone for heating mode« less

Authors:
 [1];  [1]
  1. Indiana Inst. of Technology, Inc., Fort Wayne, IN (United States)
Publication Date:
Research Org.:
Indiana Inst. of Technology, Inc., Fort Wayne, IN (United States)
Sponsoring Org.:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Geothermal Technologies Office (EE-4G); USDOE Office of Energy Efficiency and Renewable Energy (EERE), Building Technologies Office (EE-5B)
OSTI Identifier:
1319766
Report Number(s):
EE0003003
DOE Contract Number:
EE0003003
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; ground source; heat pump; HVAC; GSHP; geothermal

Citation Formats

Aschliman, Dave, and Lubbehusen, Mike. Pioneering Heat Pump Project. United States: N. p., 2015. Web. doi:10.2172/1319766.
Aschliman, Dave, & Lubbehusen, Mike. Pioneering Heat Pump Project. United States. doi:10.2172/1319766.
Aschliman, Dave, and Lubbehusen, Mike. 2015. "Pioneering Heat Pump Project". United States. doi:10.2172/1319766. https://www.osti.gov/servlets/purl/1319766.
@article{osti_1319766,
title = {Pioneering Heat Pump Project},
author = {Aschliman, Dave and Lubbehusen, Mike},
abstractNote = {This project was initiated at a time when ground coupled heat pump systems in this region were limited in size and quantity. There were economic pressures with costs for natural gas and electric utilities that had many organizations considering ground coupled heat pumps; The research has added to the understanding of how ground temperatures fluctuate seasonally and how this affects the performance and operation of the heat pumps. This was done by using a series of temperature sensors buried within the middle of one of the vertical bore fields with sensors located at various depths below grade. Trending of the data showed that there is a lag in ground temperature with respect to air temperatures in the shoulder months, however as full cooling and heating season arrives, the heat rejection and heat extraction from the ground has a significant effect on the ground temps; Additionally it is better understood that while a large community geothermal bore field serving multiple buildings does provide a convenient central plant to use, it introduces complexity of not being able to easily model and predict how each building will contribute to the loads in real time. Additional controllers and programming were added to provide more insight into this real time load profile and allow for intelligent shedding of load via a dry cooler during cool nights in lieu of rejecting to the ground loop. This serves as a means to ‘condition’ the ground loop and mitigate thermal creep of the field, as is typically observed; and It has been observed when compared to traditional heating and cooling equipment, there is still a cost premium to use ground source heat pumps that is driven mostly by the cost for vertical bore holes. Horizontal loop systems are less costly to install, but do not perform as well in this climate zone for heating mode},
doi = {10.2172/1319766},
journal = {},
number = ,
volume = ,
place = {United States},
year = 2015,
month = 6
}

Technical Report:

Save / Share:
  • Improved performance of groundwater heat pumps can be realized with a more effective and efficient utilization of the thermal properties of shallow groundwater. These systems circulate water from aquifers through water source heat pumps to achieved high efficiencies and capacities. This project concludes that a 10 to 15 percent cooling performance improvement can be realized by pre-cooling the room air with the 55/sup 0/ to 67/sup 0/F groundwater available in large portions of the Southeast. Proper design of these pre-coolers eliminates unnecessary auxiliary energy requirements. The efficiency of the overall system can be further improved with modifications to current methodsmore » of water circulation system design. Pressure requirements are minimized by maintaining a low unit inlet pressure (8 psig maximum), removing unnecessary loop restrictions and injection below the water table. Standard submersible water pumps exceed the resulting required size for residential groundwater heat pumps. Simple modifications can be made by the manufacturer to correct this problem. The result is an overall 15 to 40 percent performance improvement over high efficiency air source heat pumps with a simple payback of between 0 to 10 years in most cases.« less
  • Abstracts are presented of 73 phases of basic research carried out in biology, chemistry, and physics. (B.O.G.)
  • This booklet describes an industrial heat pump demonstration project conducted at a plant in Norwich, New York. The project required retrofitting an open-cycle heat pump to a single-effect, recirculating-type evaporator. The heat pump design uses an electrically driven centrifugal compressor to recover the latent heat of the water vapor generated by the evaporator. The compressed vapor is returned to the process, where it displaces the use of boiler steam. The goal was to reduce costs associated with operating the evaporator, which is used for reduction the water content of whey (a liquid by-product from cheese production). The retrofit equipment hasmore » now completed more than one year of successful operation. Heat pump coefficient of performance has been measured and is in the range of 14 to 18 under varying process conditions. Generalization of project results indicates that the demonstrated technology achieved attractive economics over a wide range of energy price assumptions, especially when the heat pump is applied to larger processes. 5 refs., 17 figs.« less
  • The metal hydride/chemical heat pump (MHHP) is a chemical heat pump containing two hydrides for the storage and/or recovery of thermal energy. It utilizes the heat of reaction of hydrogen with specific metal alloys. The MHHP design can be tailored to provide heating and/or cooling or temperature upgrading over a wide range of input and ambient temperatures. The system can thus be used with a variety of heat sources including waste heat, solar energy or a fossil fuel. The conceptual design of the MHHP was developed. A national market survey including a study of applications and market sectors was conducted.more » The technical tasks including conceptual development, thermal and mechanical design, laboratory verification of design and material performance, cost analysis and the detailed design of the Engineering Development Test Unit (EDTU) were performed. As a result of the market study, the temperature upgrade cycle of the MHHP was chosen for development. Operating temperature ranges for the upgrader were selected to be from 70 to 110/sup 0/C (160 to 230/sup 0/F) for the source heat and 140 to 190/sup 0/C (280 to 375/sup 0/F) for the product heat. These ranges are applicable to many processes in industries such as food, textile, paper and pulp, and chemical. The hydride pair well suited for these temperatures is LaNi/sub 5//LaNi/sub 4/ /sub 5/Al/sub 0/ /sub 5/. The EDTU was designed for the upgrade cycle. It is a compact finned tube arrangement enclosed in a pressure vessel. This design incorporates high heat transfer and low thermal mass in a system which maximizes the coefficient of performance (COP). It will be constructed in Phase II. Continuation of this effort is recommended.« less
  • Groundwater heat pumps have significantly higher efficiencies in the Texas Gulf Coast Region than conventional Heating, Ventilating, and Air Conditioning systems (HVAC). With extensive groundwater sources on the Gulf Coast, consumers can derive potential energy savings between 30 and 50 percent by switching to groundwater heat pumps. At present utility rates (1978 figures), payback periods are typically six years or less compared to gas heating and three years compared to electric heating. This study reports the investigation of heat pump technology and application in the Gulf Coast area and provides the following information: introduction to energy needs, basic heat pumpmore » technology, history of the development of groundwater heat pump systems, conceptual design of groundwater heat pump systems, regulatory and environmental considerations, and references.« less