Analysis of Radiant Cooling System Configurations Integrated with Cooling Tower for Different Indian Climatic Zones

Conference ·
OSTI ID:1319174
 [1];  [2];  [1];  [1]
  1. Malaviya National Institute of Technology (MNIT), Jaipur, India
  2. ORNL

Radiant cooling system has proven to be a low energy consumption system for building cooling needs. This study describes the use of cooling tower in radiant cooling system to improve the overall system efficiency. A comprehensive simulation feasibility study of the application of cooling tower in radiant cooling system was performed for the fifteen cities in different climatic zones of India. It was found that in summer, the wet bulb temperature (WBT) of the different climatic zones except warm-humid is suitable for the integration of cooling tower with radiant cooling system. In these climates, cooling tower can provide on average 24 C to 27 C water In order to achieve the energy saving potential, three different configurations of radiant cooling system have been compared in terms of energy consumption. The different configurations of the radiant cooling system integrated with cooling tower are: (1) provide chilled water to the floor, wall and ceiling mounted tubular installation. (2) provide chilled water to the wall and ceiling mounted tabular installation. In this arrangement a separate chiller has also been used to provide chilled water at 16 C to the floor mounted tubular installation. (3) provide chilled water to the wall mounted tabular installation and a separate chiller is used to provide chilled water at 16 C to the floor and ceiling mounted tabular installation. A dedicated outdoor air system is also coupled for dehumidification and ventilation in all three configurations. A conventional all-air system was simulated as a baseline to compare these configurations for assessing the energy saving potential.

Research Organization:
Oak Ridge National Laboratory (ORNL), Oak Ridge, TN (United States)
Sponsoring Organization:
EE USDOE - Office of Energy Efficiency and Renewable Energy (EE)
DOE Contract Number:
AC05-00OR22725
OSTI ID:
1319174
Country of Publication:
United States
Language:
English

Similar Records

Analysis of radiant cooling system integrated with cooling tower for composite climatic conditions
Conference · Wed Feb 28 23:00:00 EST 2018 · OSTI ID:1456822

Calibrated simulation analysis for integration of evaporative cooling and radiant cooling system for different Indian climatic zones
Journal Article · Thu May 31 00:00:00 EDT 2018 · Journal of Building Engineering · OSTI ID:1474738

PERFORMANCE EVALUATION OF CEILING RADIANT COOLING SYSTEM IN COMPOSITE CLIMATE
Conference · Wed Dec 31 23:00:00 EST 2014 · OSTI ID:1236588

Related Subjects