Two-phase pressure drop of refrigerants during flow boiling in small channels : an experimental investigation and correlation development.

Conference ·
OSTI ID:12396
Two-phase flow pressure drop measurements were made during a phase-change heat transfer process with three refrigerants (R-134a, R-12, and R-113) at six different pressures ranging from 138 kPa to 856 kPa, and in two sizes of round tubes (2.46 mm and 2.92 mm inside diameters) and one rectangular channel (4.06 x 1.7 mm). State-of-the-art large-tube correlations failed to satisfactorily predict the experimental data. The data were used to develop a new correlation for two-phase pressure drop during flow boiling in small channels. The correlation was then tested against the experimental data for the three refrigerants; the error was {+-}20%.
Research Organization:
Argonne National Lab., IL (US)
Sponsoring Organization:
US Department of Energy (US)
DOE Contract Number:
W-31109-ENG-38
OSTI ID:
12396
Report Number(s):
ANL/ET/CP-98230
Country of Publication:
United States
Language:
English

Similar Records

Boiling heat transfer with three fluids in small circular and rectangular channels
Technical Report · Sat Dec 31 23:00:00 EST 1994 · OSTI ID:93485

Two-phase frictional pressure drop of R-134a and R-410A refrigerant-oil mixtures in straight tubes and U-type wavy tubes
Journal Article · Wed Feb 14 23:00:00 EST 2007 · Experimental Thermal and Fluid Science · OSTI ID:20843288

Evaporation heat transfer and pressure drop of refrigerant R-134a in a plate heat exchanger
Journal Article · Sun Jan 31 23:00:00 EST 1999 · Journal of Heat Transfer · OSTI ID:343651