Effect of copper and silver ionization on Legionella pneumophila eradication
Book
·
OSTI ID:116308
- Univ. of Pittsburgh, PA (United States)
- VA Medical Center, Pittsburgh, PA (United States)
The presence of Legionella pneumophila in water distribution systems has been epidemiologically linked to hospital-acquired Legionnaires` disease. The objective of this study was to evaluate the efficiency of copper and silver ions for inactivation of Legionella pneumophila. Experimental results showed that L. pneumophila was completely inactivated at copper concentration of 0.1 mg/L within the period of 2.5 hours while 6-log reduction requires a Ct value of 0.8 mg/L*hour. On the other hand, more than 24 hours was required to completely eradicate L. pneumophila at the highest silver ion concentration (0.08 mg/L) tested and only 4-log reduction is observed for Ct value of 0.8 mg/L*hour. The effective synergism of these ions in eradicating L. pneumophila was observed for copper concentrations of 0.05 and silver concentration of 0.04 mg/L. One approach for the control of L. pneumophila in water distribution systems is to initiate copper/silver ion concentrations at 0.4/0.04 mg/L to achieve complete eradication of L. pneumophila already present in the water distribution system (as established in previous studies) followed by a lower residual (0.05/0.04 mg/L) protection against L. pneumophila in the incoming water.
- OSTI ID:
- 116308
- Report Number(s):
- CONF-9507173--; ISBN 0-7844-0095-4
- Country of Publication:
- United States
- Language:
- English
Similar Records
Efficacy of copper and silver ions and reduced levels of free chlorine in inactivation of Legionella pneumophila
Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system
The Impact of Storms on Legionella pneumophila in Cooling Tower Water, Implications for Human Health
Journal Article
·
Thu Nov 30 23:00:00 EST 1989
· Applied and Environmental Microbiology; (USA)
·
OSTI ID:5837939
Comparative assessment of chlorine, heat, ozone, and UV light for killing Legionella pneumophila within a model plumbing system
Journal Article
·
Sat Jan 31 23:00:00 EST 1987
· Appl. Environ. Microbiol.; (United States)
·
OSTI ID:6516596
The Impact of Storms on Legionella pneumophila in Cooling Tower Water, Implications for Human Health
Journal Article
·
Wed Dec 09 23:00:00 EST 2020
· Frontiers in Microbiology
·
OSTI ID:1766464