Advanced Rooftop Control (ARC) Retrofit: Field-Test Results

Technical Report ·
DOI:https://doi.org/10.2172/1096129· OSTI ID:1096129
The multi-year research study was initiated to find solutions to improve packaged equipment operating efficiency in the field. Pacific Northwest National Laboratory (PNNL), with funding from the U.S. Department of Energy’s (DOE’s) Building Technologies Office (BTO) and Bonneville Power Administration (BPA) conducted this research, development and demonstration (RD&D) study. Packaged equipment with constant speed supply fans is designed to provide ventilation at the design rate at all times when the fan is operating as required by building code. Although there are a number of hours during the day when a building may not be fully occupied or the need for ventilation is lower than designed, the ventilation rate cannot be adjusted easily with a constant speed fan. Therefore, modulating the supply fan in conjunction with demand controlled ventilation (DCV) will not only reduce the coil energy but also reduce the fan energy. The objective of this multi-year research, development and demonstration project was to determine the magnitude of energy savings achievable by retrofitting existing packaged rooftop air conditioners with advanced control strategies not ordinarily used for packaged units. First, through detailed simulation analysis, it was shown that significant energy (between 24% and 35%) and cost savings (38%) from fan, cooling and heating energy consumption could be realized when packaged air conditioning units with gas furnaces are retrofitted with advanced control packages (combining multi-speed fan control, integrated economizer controls and DCV). The simulation analysis also showed significant savings for heat pumps (between 20% and 60%). The simulation analysis was followed by an extensive field test of a retrofittable advanced rooftop unit (RTU) controller.
Research Organization:
Pacific Northwest National Laboratory (PNNL), Richland, WA (United States)
Sponsoring Organization:
USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
DOE Contract Number:
AC05-76RL01830
OSTI ID:
1096129
Report Number(s):
PNNL--22656; 400480000
Country of Publication:
United States
Language:
English

Similar Records

End-Use Savings Shapes Measure Documentation: Advanced Rooftop Unit Control
Technical Report · Wed May 01 20:00:00 EDT 2024 · OSTI ID:2348903

Field evaluation of advanced controls for the retrofit of packaged air conditioners and heat pumps
Journal Article · Tue Sep 01 00:00:00 EDT 2015 · Applied Energy, 154:344-351 · OSTI ID:1184291

Energy performance evaluation of variable-speed packaged rooftop units using field measurements and building energy simulation
Journal Article · Mon Dec 31 23:00:00 EST 2018 · Energy and Buildings · OSTI ID:1501832

Related Subjects