System Modeling of Gas Engine Driven Heat Pump
Conference
·
OSTI ID:1081918
- Oak Ridge National Laboratory (ORNL)
- ORNL
To improve the system performance of the GHP, modeling and experimental study has been made by using desiccant system in cooling operation (particularly in high humidity operations) and suction line waste heat recovery to augment heating capacity and efficiency. The performance of overall GHP system has been simulated by using ORNL Modulating Heat Pump Design Software, which is used to predict steady-state heating and cooling performance of variable-speed vapor compression air-to-air heat pumps for a wide range of operational variables. The modeling includes: (1) GHP cycle without any performance improvements (suction liquid heat exchange and heat recovery) as a baseline (both in cooling and heating mode), (2) the GHP cycle in cooling mode with desiccant system regenerated by waste heat from engine incorporated, (3) GHP cycle in heating mode with heat recovery (recovered heat from engine). According to the system modeling results, by using desiccant system regenerated by waste heat from engine, the SHR can be lowered to 40%. The waste heat of the gas engine can boost the space heating efficiency by 25% in rated operating conditions.
- Research Organization:
- Oak Ridge National Laboratory (ORNL); Building Technologies Research and Integration Center
- Sponsoring Organization:
- EE USDOE - Office of Energy Efficiency and Renewable Energy (EE)
- DOE Contract Number:
- AC05-00OR22725
- OSTI ID:
- 1081918
- Country of Publication:
- United States
- Language:
- English
Similar Records
System Modeling and Building Energy Simulations of Gas Engine Driven Heat Pump
Gas Engine-Driven Heat Pump with Desiccant Dehumidification
Performance of Gas-Engine Driven Heat Pump Unit
Journal Article
·
Mon Dec 31 23:00:00 EST 2012
· HVAC & R Research
·
OSTI ID:1157153
Gas Engine-Driven Heat Pump with Desiccant Dehumidification
Conference
·
Sat Dec 31 23:00:00 EST 2016
·
OSTI ID:1338549
Performance of Gas-Engine Driven Heat Pump Unit
Technical Report
·
Tue Sep 30 00:00:00 EDT 2008
·
OSTI ID:975486