Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Energy efficient indoor VOC air cleaning with activated carbon fiber (ACF) filters

Journal Article · · Building and Environment

This study explores the potential environmental and energy benefits of using activated carbon fiber (ACF) filters for air cleaning in HVAC systems. The parallel aims for the air cleaning system were to enable reduced indoor exposures to volatile organic compounds (VOCs) and to simultaneously allow reduced rates and energy consumption for outdoor-air ventilation. We evaluated the use of ACF media to adsorb VOCs from indoor air during repeated simulated 12-hour to 24-hour periods of occupancy. In a cyclic regeneration process, VOCs were desorbed from the ACF media and vented outdoors to enable the next cycle of air cleaning. The VOC removal efficiency of the ACF media was measured using a 9.5-cm2 ACF specimen exposed to a mixture of VOCs that included toluene, benzene, o-xylene, 1-butanol, limonene, undecane and formaldehyde at 29 °C and 30 percent relative humidity. The concentrations of these model pollutants upstream of the ACF media were in the range 20 to 30 ppb, to simulate realistic conditions. Velocities through the ACF media were typical of those in normal particle filter systems (~ 0.5 m s-1). Initial tests were conducted to develop a modified multi-component Freundlich isotherm and estimate the maximum adsorption capacity of the media, which was determined to be 90 mg VOC per gram of ACF. Three different ACF regeneration methods were explored using relatively cleaner outdoor air under ambient conditions, with this air humidified, and with the filter heated. It was found that heating the ACF media to ~150 °C by circulation of a DC current through the fibers for a short period (15 minutes) yielded the best VOC removal results, allowing for subsequent consistent removal efficiencies of 70-80 percent for most VOCs. Regeneration with unheated outdoor air was also effective and used less energy (subsequent removal efficiency was 50-60 percent for most VOCs). ACF did not perform as well in eliminating formaldehyde, for which a maximum removal of 25-30 percent was achieved with heated regeneration. A mass balance model indicated that the combination of ACF air cleaning and a 50percent reduction in ventilation will decrease indoor concentrations of VOCs by 60 percent to 80 percent and reduce formaldehyde concentrations by 12 percent to 40 percent. Energy modeling indicated the potential to reduce the energy required for heating and cooling of ventilation air by 35 percent to almost 50 percent.

Research Organization:
Ernest Orlando Lawrence Berkeley National Laboratory, Berkeley, CA (US)
Sponsoring Organization:
USDOE
DOE Contract Number:
AC02-05CH11231
OSTI ID:
1051834
Report Number(s):
LBNL-5176E
Journal Information:
Building and Environment, Journal Name: Building and Environment Vol. 47; ISSN 0360-1323
Publisher:
Elsevier
Country of Publication:
United States
Language:
English

References (14)

Organic Vapor Recovery and Energy Efficiency during Electric Regeneration of an Activated Carbon Fiber Cloth Adsorber journal March 2004
Evaluation of various activated carbons for air cleaning – Towards design of immune and sustainable buildings journal November 2008
Investigation of the Treatability of the Primary Indoor Volatile Organic Compounds on Activated Carbon Fiber Cloths at Typical Indoor Concentrations journal July 2009
Assessing the performance of air cleaning devices – A full-scale test method journal January 2010
Vapor-Phase Adsorption of Hexane and Benzene on Activated Carbon Fabric Cloth:  Equilibria and Rate Studies journal May 2002
Removal of volatile organic compound by activated carbon fiber journal January 2004
Adsorption and Electrothermal Desorption of Hazardous Organic Vapors journal March 2001
Adsorption and Regeneration on Activated Carbon Fiber Cloth for Volatile Organic Compounds at Indoor Concentration Levels journal January 2009
Gas Phase Adsorption of Volatile Organic Compounds and Water Vapor on Activated Carbon Cloth journal March 1997
A Freundlich-type multicomponent isotherm journal January 1981
Modeling of Adsorption and Regeneration of Volatile Organic Compounds on Activated Carbon Fiber Cloth journal December 2009
Equilibrium and Heat of Adsorption for Organic Vapors and Activated Carbons journal June 2005
Adsorption of Toluene onto Activated Carbon Fibre Cloths and Felts: Application to Indoor Air Treatment journal November 2005
Adsorption onto Activated Carbon Cloths and Electrothermal Regeneration: Its Potential Industrial Applications journal March 2004