Foundation heat exchangers for residential ground source heat pump systems Numerical modeling and experimental validation
- Oklahoma State University
- ORNL
A new type of ground heat exchanger that utilizes the excavation often made for basements or foundations has been proposed as an alternative to conventional ground heat exchangers. This article describes a numerical model that can be used to size these foundation heat exchanger (FHX) systems. The numerical model is a two-dimensional finite-volume model that considers a wide variety of factors, such as soil freezing and evapotranspiration. The FHX numerical model is validated with one year of experimental data collected at an experimental house located near Oak Ridge, Tennessee. The model shows good agreement with the experimental data-heat pump entering fluid temperatures typically within 1 C (1.8 F) - with minor discrepancies due to approximations, such as constant moisture content throughout the year, uniform evapotranspiration over the seasons, and lack of ground shading in the model.
- Research Organization:
- Oak Ridge National Lab. (ORNL), Oak Ridge, TN (United States). Building Technologies Research and Integration Center (BTRIC)
- Sponsoring Organization:
- USDOE
- DOE Contract Number:
- DE-AC05-00OR22725
- OSTI ID:
- 1037688
- Journal Information:
- HVAC & R Research, Vol. 17, Issue 6; ISSN 1078-9669
- Country of Publication:
- United States
- Language:
- English
Similar Records
Foundation Heat Exchanger Final Report: Demonstration, Measured Performance, and Validated Model and Design Tool
Demonstration and Performance Monitoring of Foundation Heat Exchangers (FHX) in Ultra-High Energy Efficient Research Homes