Title: Testing of a cryogenic recooler heat exchanger at Brookhaven National Laboratory

Conference ·
OSTI ID:10184607

Brookhaven National Laboratory has tested a recooler heat exchanger intended to be used in the cryogenic system of the Relativistic Heavy Ion Collider. The unit is required to transfer 225 Watts from a supercritical helium stream flowing at 100 g/s to a helium bath boiling at 4.25 K. Measurements made with heat loads of 50 to over 450 Watts on the unit indicate its cooling capacity is greater than 400 Watts, as expected, and it will be suitable for use in the RHIC ring. Presented are the modifications made to BNL`s MAGCOOL test facility that were necessary for testing, test procedure, and recooler performance.

Research Organization:
Brookhaven National Lab., Upton, NY (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC02-76CH00016
OSTI ID:
10184607
Report Number(s):
BNL-49347; CONF-930703-28; ON: DE93040166; TRN: 93:022848
Resource Relation:
Conference: International cryogenic materials conference (ICMC),Albuquerque, NM (United States),12-16 Jul 1993; Other Information: PBD: [1993]