Preliminary evaluation of the performance, water use, and current application trends of evaporative coolers in California climates

Technical Report ·
DOI:https://doi.org/10.2172/10159978· OSTI ID:10159978
This paper describes the latest results of an ongoing analysis investigating the potential for evaporative cooling as an energy-efficient alternative to standard air-conditioning in California residences. In particular, the study uses detailed numerical models of evaporative coolers linked with the DOE-2 building energy simulation program to study the issues of indoor comfort, energy and peak demand savings with and without supplemental air-conditioning and consumptive water use. In addition, limited surveys are used to assess the current market availability of evaporative cooling in California, typical contractor practices and costs, and general acceptance of the technology among engineers, contractors, and manufacturers. The results show that evaporative coolers can provide significant energy and peak demand savings in California residences, but the impact of the increased indoor humidity on human comfort remains an unanswered question that requires further research and clarification. Evaluated against ASHRAE comfort standards developed primarily for air-conditioning both direct and two-stage evaporative coolers would not maintain comfort at peak cooling conditions due to excessive humidity. However, using bioclimatic charts that place human comfort at the 80% relative humidity line, the study suggests that direct evaporative coolers will work in mild coastal climates, while two-stage models should provide adequate comfort in Title 24 houses throughout California, except in the Imperial Valley. The study also shows that evaporative coolers will increase household water consumption by less than 6% on an annual basis, and as much as 23% during peak cooling months, and that the increases in water cost are minimal compared to the electricity savings. Lastly, a survey of engineers and contractors revealed generally positive experiences with evaporative coolers, with operational cost savings, improved comfort, unproved air quality as the primary benefits in their use.
Research Organization:
Lawrence Berkeley Lab., CA (United States)
Sponsoring Organization:
USDOE, Washington, DC (United States)
DOE Contract Number:
AC03-76SF00098
OSTI ID:
10159978
Report Number(s):
LBL--32826; ON: DE93015235
Country of Publication:
United States
Language:
English

Similar Records

Evaporative cooling: A nationwide low-energy alternative
Journal Article · Wed Dec 31 23:00:00 EST 1986 · Passive Sol. J.; (United States) · OSTI ID:6978058

Mathematical model and experimental validation of a rock bed regenerative cooler
Conference · Mon Dec 31 23:00:00 EST 1979 · Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States) · OSTI ID:6541316

NREL's Energy-Saving Technology for Air Conditioning Cuts Peak Power Loads Without Using Harmful Refrigerants (Fact Sheet)
Technical Report · Sat Jun 30 20:00:00 EDT 2012 · OSTI ID:1046261